I have had to replace a radiator upstairs in bathroom.I drained all out let pipes and did the job.On testing the upstairs rads were ok but downstairs 2 wont get hot.They were ok before.I have bled all but no luck.Thanks
Gravatar

Answers

1 to 6 of 6rss feed

Best Answer

No best answer has yet been selected by picker. Once a best answer has been selected, it will be shown here.

For more on marking an answer as the "Best Answer", please visit our FAQ.
If just replacing an upstairs rad, why did you drain the downstairs as well? The method is to drain just enough to take the water level below the highest point.
How long since you have completed the job. Air dispelled from fresh water can take a few days to clear. Continual bleeding might be required.
Try turning off all other rads, leaving on the problem one and run the system.
Was it replaced with an identical radiator ? Do the downstairs ones get warm ? Maybe the disturbance caused a block and the system needs flushing ? Try bumping up the pump pressure see if you can push things through. If you bled at the radiators, check for vents to see if you can release air there.
Did I really take more than 3 minutes to type that ?
Question Author
Thanks for your help I will try tonight a see what happens.
Did you drain the whole system down, picker?
If so, go around the whole house and bleed again.
Question Author
Turned off the upstairs rads bleed downstairs again and hey presto all working ok THANKS ALL.