Depends on the size of the cable running to the storage rads.
It will either be 2.5mm square area or 4mm square area (2.5mm square is the size of a normal ring main cable).
If he's got a radial circuit and he's got 2.5mm cable, protect each circuit with a 16A MCB and fit one double socket on the end of each.
If he's got 4mm square cable and a radial circuit, still protect with a 16A and put one double socket on the end - because one isn't allowed more than one double on a spur. The cabling size of 4mm would cope with up to 32A load, but there's no point upping the breaker size.