haway | 12:22 Fri 20th Dec 2013 | Home & Garden
8 Answers
The subject may be explanation enough ? My boiler has, like many others, exhibited a fault which is displayed as "F9"; it is common, but seemingly impossible to cure ? Each morning, it shows F9, I can start the boiler by injecting a shot of water, and away it goes, all day, no problem- until tomorrow!
I had the same fault last winter, the pressure switch was changed then, it got through the winter until a few weeks ago. Can anyone possitively define the fault ? Even my heating engineer is struggling with it.
Gravatar

Answers

1 to 8 of 8rss feed

Best Answer

No best answer has yet been selected by haway. Once a best answer has been selected, it will be shown here.

For more on marking an answer as the "Best Answer", please visit our FAQ.
This boiler is known for it, haway. Expensive to maintain as well. If it's old enough, I would seriously consider replacing it with something sensible.

Faulty pressure switch usually, also ......... pressure sensor; stuck circulating pump; bunged-up pump filter; plus the inevitable possibility of circuit board fault.

F9 seems to be a catch-all fault code when something is wrong (or wrongly sensed as faulty) on the water pressure side.

I'm afraid that no one (probably even Glowworm) can give you a definitive answer. I would check the pump and filter, and maybe try another pressure switch.

When it's drained down, the pressure gauge should read "0". If there is still a reading of some sort, then that would indicate a faulty pressure sensor.
I've seen this many times before, if the pressure keeps dropping there is a leak somewhere
........ often, dekky, but not necessarily. A faulty pressure switch/sensor will cause the system to "blow off" the pressure, thus expelling water.
A faulty pressure vessel, or one that need re-charging (pumping up) will have the same result.
T B ..Very true but if it is the pressure valve"blowing off" there will be a stained/wet patch where the pipe comes out of the wall.
Since you are increasing the system pressure each morning, this would suggest to me that you have a leak somewhere in the system – and that the displayed F9 is a genuine low pressure fault/indication.

What is the pressure reading before you add a ‘shot of water’ to fix the problem? The system has a minimum pressure of 0.7bar and recommended at 1.0bar.
Question Author
Thank you all for your input; as for questions on pressure, as I said, it's the only way to get the boiler to fire up, there are no leaks, I have to drain off water as the pressure builds up; it works at anything up to 2.5 bar, at which point, I get nervous and bleed pressure off. I tend to agree with the suggestion of a replacement, this one is only 6 years old, however, I would like to hang on until warmer weather before anything drastic.....
Hey haway,

Did you finally manage to cure that f9? (guess why I ask...)
F9 error on SX18 means Low water pressure sensor detected a drop in water pressure and the boiler wouldn't start. https://www.glow-worm.co.uk/trade/service-support/fault-finding-codes/subsites/betacom-a-range-9-233377.html


This may help:-
http://heatingforce.co.uk/blog/boiler-losing-pressure/