Quizzes & Puzzles0 min ago
Fuse and Ringmains
Answers
No best answer has yet been selected by ewand. Once a best answer has been selected, it will be shown here.
For more on marking an answer as the "Best Answer", please visit our FAQ.Absolutely not - even if the correct circuit protection rating is used (I.e. 30 or 32A). Whilst it would work, there are limitations on the recommended area served by a domestic ring main - 100 sq metres, you could also exceed the maximum demand of the protective device.
If the protective device trips, you will lose both rings. And many other good reasons.
Not sure I understand what you mean by stud ? Study ? Are you just wanting to add more sockets to an existing ring ?
The general rules are - maximum floor area of 100 sq metres per ring (in theory as many sockets as you like). Look at the diversity and ensure that the maximum potential load won't exceed the rating of the protective device.
Kitchens should ideally be on a separate ring. You could consider a radial circuit. There are also rules regarding the number of unfused spurs and fused fixed appliances off a ring.
OK - well you are allowed spurs on the ring up to the number of directly connected sockets and directly connected fixed appliances. I wouldn't personally recommend going to these maximums but those are the rules.
Each spur should feed no more than a single or double socket or one fixed appliance.
Basically look at the potential load and decide whether to split into a separate ring with a separate fuse/breaker at the board.
Hope that helps.
Related Questions
Sorry, we can't find any related questions. Try using the search bar at the top of the page to search for some keywords, or choose a topic and submit your own question.