ChatterBank14 mins ago
glow-worm flexicom 15hx boiler
4 Answers
the boiler sometimes flashes an F22 fault. The manual is of no help and the engineer doesn't know what it is. We always re-set it and all's ok but it still comes back from time to time. It's only a year old and otherwise fine. Can anyone advise what fault F22 is? Thank you
Answers
Best Answer
No best answer has yet been selected by janbee. Once a best answer has been selected, it will be shown here.
For more on marking an answer as the "Best Answer", please visit our FAQ.hi jan
F22 is Low Water pressure or Ignition temperature rise to slow
likely causes are
Not enough water in the system.
Central Heating Flow or Return
Thermistor wires loose, faulty, trapped.
Central Heating Flow or Return Thermistor not connected to pipe correctly.
Air in the system.
Faulty pump or pump speed to fast.
This info should help your engineer
F22 is Low Water pressure or Ignition temperature rise to slow
likely causes are
Not enough water in the system.
Central Heating Flow or Return
Thermistor wires loose, faulty, trapped.
Central Heating Flow or Return Thermistor not connected to pipe correctly.
Air in the system.
Faulty pump or pump speed to fast.
This info should help your engineer