Editor's Blog1 min ago
Radial Power Circuits - Upgrading
9 Answers
One for Bright Spark or another qualified person.
If a dwelling has been rewired 30 years ago from its original (1920s) radial configuration, not converted to ring circuits for power sockets, is there an obligation to convert to rings when upgrading the CU to MCBs plus RCD.
Research suggests radial circuits can be acceptable under 17th Edition?
If a dwelling has been rewired 30 years ago from its original (1920s) radial configuration, not converted to ring circuits for power sockets, is there an obligation to convert to rings when upgrading the CU to MCBs plus RCD.
Research suggests radial circuits can be acceptable under 17th Edition?
Answers
Radials fine provided correct rating breaker is used - 20A for a radial, rather than 32A for a ring. UK are about the only ring users left in the world....
21:28 Fri 05th Sep 2014
BM..radials have several advantages over rings
You can wire 2 radials using almost as much cable as 1 ring
If one radial trips you still have the other
Instead of having a 32a current rating(as on a ring)you will now have a total of 40a (2 x 20)
You could wire the radials in 4mm cable giving you a 32a capacity on each radial.
Testing is simplified with radial circuits also.
You can wire 2 radials using almost as much cable as 1 ring
If one radial trips you still have the other
Instead of having a 32a current rating(as on a ring)you will now have a total of 40a (2 x 20)
You could wire the radials in 4mm cable giving you a 32a capacity on each radial.
Testing is simplified with radial circuits also.
BS, thank you for the additional clarification. The dwelling in question is already wired as a radial in PVC, replacing the original rubber insulation cable. What I don't want to have to do is rewire again when the CU is upgraded, and was wanting to check the Regs. I'll check, but I think the existing is 2.5mm squared cable, as the existing cartridge fuses are 15A. Assume that one fits a 16A MCB on each radial circuit.
I'm also clear the work needs Part P Building Regs.
I'm also clear the work needs Part P Building Regs.
Without going too deep into the regs,there is a requirement that the radial circuits cannot serve more than a certain m2 of floor space.However in most domestic situations the breach would be unlikely.You should be ok with a 20a 'b' type mcb....though I would use BS 61009 RCBO units for each circuit as these will give full overcurrent and earth leakage protection to each circuit separately .....(they are becoming cheaper).
Related Questions
Sorry, we can't find any related questions. Try using the search bar at the top of the page to search for some keywords, or choose a topic and submit your own question.