Donate SIGN UP

Mira Sport Shower 7.5, 9.0 & 9.8 Kw

Avatar Image
slipnot | 10:31 Thu 29th Dec 2022 | Home & Garden
4 Answers
The electric over-bath shower keeps blowing fuses after a few weeks. The instruction manual says to use a 40amp fuse but I can't find one anywhere (B&Q, Internet etc). A 45amp fuse is too big to fit in box, and I'm currently using 30amp fuses which blow within weeks. Contacted Mira by email who advise me to call a local electrician.. anyone else had this problem .. any advice would be appreciated.
Gravatar

Answers

1 to 4 of 4rss feed

Best Answer

No best answer has yet been selected by slipnot. Once a best answer has been selected, it will be shown here.

For more on marking an answer as the "Best Answer", please visit our FAQ.
It sounds like you have a very old system.You can only use a 45a fuse if the cable feeding the shower is 10mm2 or larger.Do you have a working RCD unit to provide earth fault protection? Go with Mira's advise...get a competent electrician to check things out.
Question Author
Thank you Ryzen ... for taking time to reply. Yes I do have an RCD unit .. shower fusebox is separate from house fuse unit. Unfortunately 45 amp is too thick to fit in so I will get an electrician to look at it after New Year. Thank you again.
If you can only fit a 30a fuse into the carrier then its quite possible that a 6mm2 cable is installed.If a larger shower has been fitted than that of the original you may need to uprate the cable and the protection.
Question Author
Thank you again Ryzen. I agree ... I will contact local approved electrician and get it all done safely. Many thanks

1 to 4 of 4rss feed

Do you know the answer?

Mira Sport Shower 7.5, 9.0 & 9.8 Kw

Answer Question >>