News0 min ago
Wiring to a type of street lamp standard
9 Answers
Can anyone tell me where I can see a wiring diagram to suit these items controlling a sodium bulb on a street lamp.
Ballast unit
Capacitor
Igniter
Crompton High Pressure Sodium Lucalox Lamp
Ballast unit
Capacitor
Igniter
Crompton High Pressure Sodium Lucalox Lamp
Answers
Best Answer
No best answer has yet been selected by Hard@it. Once a best answer has been selected, it will be shown here.
For more on marking an answer as the "Best Answer", please visit our FAQ.mmm i'll not ask why? but
usually
live to ballast then to igniter
igniter to lamp
neutral to both igniter and lamp
power factor capacitor across supply (L & N)
or sometimes if its a three terminal ballast
live to ballast and to igniter
ballast to lamp
ballast to igniter
neutral to both igniter and lamp
power factor capacitor across supply (L & N)
and there are other ways
but have a look at the ballast as the wiring diagram is usually printed on it
usually
live to ballast then to igniter
igniter to lamp
neutral to both igniter and lamp
power factor capacitor across supply (L & N)
or sometimes if its a three terminal ballast
live to ballast and to igniter
ballast to lamp
ballast to igniter
neutral to both igniter and lamp
power factor capacitor across supply (L & N)
and there are other ways
but have a look at the ballast as the wiring diagram is usually printed on it
Hi matt1E, thanks for your reply. There is nothing sinister in this, we are 16 houses in a small estate and are responsible for 4 street lamps and 2 pend lights. Through the 11 years we have changed the occasional bulb but this time it did not work. We then changed the Ballast, Cap., and Igniter, changing conn.for conn., but no reaction!
Ours is as your 3 terminal guide with the Ballast having four terminals and using only the three.
Thanks for your time on this, but all is as you say, will prob. have to bring in the Council man as do not know any other street lighting person.
Cheers Hard@it
Ours is as your 3 terminal guide with the Ballast having four terminals and using only the three.
Thanks for your time on this, but all is as you say, will prob. have to bring in the Council man as do not know any other street lighting person.
Cheers Hard@it
have you checked the photo cell on the top?
also high pressure sodium are very "fussy" about starting when there are corroded or bad connections so remake the ends and especially check the centre pin on the lamp holder it may need pulling up a bit but make sure the power is of and the capacitor is either discharged or disconnected while you do this
also high pressure sodium are very "fussy" about starting when there are corroded or bad connections so remake the ends and especially check the centre pin on the lamp holder it may need pulling up a bit but make sure the power is of and the capacitor is either discharged or disconnected while you do this
also on thinking make sure you have not bought a lamp with a internal igniter as this will not work and will probably damage the ballast. Its easy to tell ,if you look at the lamp there will be a symbol on it that looks like a triangle it will either have an E or a I in the middle you need to have an E for external igniter
the I stands for Internal and you don't want one of these
the I stands for Internal and you don't want one of these
matt1e, the switching is done by a light sensor, remote from the lights and controls all. The Triangle has an E on the lamps. Your point re the centre pin is a good one and after making sure re capacitor I will check this. Poss tomorrow as we are getting high winds here and it's not the best for up a scaffold. Will let you know re outcome.
oops forgot the link
http://www.venturelighting.com/TechCenter/trou bleshooting.html
http://www.venturelighting.com/TechCenter/trou bleshooting.html
matt1e, just to let you know I got the expert in to check out the controls we fitted. He said that the igniter I was given to replace existing was not suitable for the purpose, the correct one was obtained and worked no bother. so you were right in your assumption that igniter could be wrong - but the triangle was correct - it was the duty of it that was wrong. Cheers and thanks again Hard@it.
Related Questions
Sorry, we can't find any related questions. Try using the search bar at the top of the page to search for some keywords, or choose a topic and submit your own question.