Can I buy a 'trip fuse' for an old style fuse box?
8 Answers
We have an old style fuse box i.e. just bog standard fuses which blow rather than trip.
For some reason when our living room light bulb goes it blows the fuse which costs several pounds to replace.
Can I buy some sort of trip fuse to slot in the box so that when a bulb next goes it only trips the fuse and doesnt blow it?
Thx.
For some reason when our living room light bulb goes it blows the fuse which costs several pounds to replace.
Can I buy some sort of trip fuse to slot in the box so that when a bulb next goes it only trips the fuse and doesnt blow it?
Thx.
Answers
Best Answer
No best answer has yet been selected by Mattk. Once a best answer has been selected, it will be shown here.
For more on marking an answer as the "Best Answer", please visit our FAQ.like this?
http://www.screwfix.c...A-SP-Type-B-Curve-MCB
(obviously get ones of the correct amp rating)
http://www.screwfix.c...A-SP-Type-B-Curve-MCB
(obviously get ones of the correct amp rating)
If your fuseboard is made by Wylex/ Mem/ Hagar then yes you can possibly get a retrofit mcb to replace your exsisting fuse.However I feel that you should be saving your money to have the system upgraded to a dual Rcd/Mcb or Rcbo unit.These will protect you and your system from earth leakage faults as well as short circuit/overcurrent faults and will be compliant with BS7671 17TH EDITION.Let me know the make/model/age of your fuseboard.
-- answer removed --
I would agree with Bright Spark – you would be better off replacing the complete consumer unit rather that swapping each fuse for an mcb. When you look at the price of replacing all the fuses with mbc’s versus a new unit (with rcd), there will not be a great deal of difference in price (including fitting).
I agree with you 316 this is a characteristic of B curve 6a mcb's and 6a BS 1361/1362 fuses.When a lamp (thats not internally fused)fails or blows it attracts a heavier than normal inrush current.This is why the device trips or fuses.It is not a fault just an inconvenience.It can be sometimes rectified by installing a 10a device ...but only if the system design will allow.