ChatterBank0 min ago
I have a new valiant ecotec 615 combi boiler. We had to turn the water off due to a leak in a pipe which has been repaired. When turning the waterr mains back on the boiler won't fire up because the water pressure is below o.1 bar. Instructions tell us to
5 Answers
Refill the boiler but there is no loop or tap to turn water on anywhere in or near the system. Can anybody help .?
Answers
Best Answer
No best answer has yet been selected by Minnief. Once a best answer has been selected, it will be shown here.
For more on marking an answer as the "Best Answer", please visit our FAQ.
-- answer removed --
Every Combi boiler has a fill loop - either one that is permanently attached with a couple of valve taps in-line to turnoff the supply from the cold water feed - or (more often) some form of temporary pipe to connect the cold feed to the sealed system. Until you refill the pressure in the system to around 0.5 bar at least, the boiler will not start
Down load the user manual here - shows you how to refill.
http://www.vaillant.c...9/43/00/838402_06.pdf
http://www.vaillant.c...9/43/00/838402_06.pdf
Related Questions
Sorry, we can't find any related questions. Try using the search bar at the top of the page to search for some keywords, or choose a topic and submit your own question.