ChatterBank1 min ago
electric shower
3 Answers
i want to fit a mira electric shower ,probably the thermostatic sport model,i have 6mm cable in to the bathroom and have a 40 amp breaker, what is the maximum shower rating i can fit ?
Answers
Best Answer
No best answer has yet been selected by cornflake. Once a best answer has been selected, it will be shown here.
For more on marking an answer as the "Best Answer", please visit our FAQ.According to this information from Mira,
9.0 kw
http://www.mirashowers.com/onlinecatalog/pdf/p 3278_4a.pdf
See para2.4
9.0 kw
http://www.mirashowers.com/onlinecatalog/pdf/p 3278_4a.pdf
See para2.4
There is no way on God's earth I would be using 6mm cable for a 9kw electric shower - An electrician friend of mine recommends 10mm otehrwise you will end up heating up more than the water.
The current load on 9kw -39.1 amps so your breaker size will need increased ( an RCBO ) would be ideal.
Please consult a qualified electrician and not some pratt who thinks they know what they're doing.
A useful guide is pasted below -
http://www.tlc-direct.co.uk/Technical/Charts/V oltageDrop.html
All the best.
The current load on 9kw -39.1 amps so your breaker size will need increased ( an RCBO ) would be ideal.
Please consult a qualified electrician and not some pratt who thinks they know what they're doing.
A useful guide is pasted below -
http://www.tlc-direct.co.uk/Technical/Charts/V oltageDrop.html
All the best.