Donate SIGN UP

Topping up CH Combi Boiler

Avatar Image
ls177hq | 01:02 Fri 06th Oct 2006 | Home & Garden
5 Answers
Hi, I have an Ideal Mini boiler and when the central heating is off the water pressure shows as being almost zero bar. Is this right, I recently bled the radiator in the attic and air came out but no water despite waiting ages. It seems to be working ok heat wise but I don't want to cause long term damage. Thanks
Gravatar

Answers

1 to 5 of 5rss feed

Best Answer

No best answer has yet been selected by ls177hq. Once a best answer has been selected, it will be shown here.

For more on marking an answer as the "Best Answer", please visit our FAQ.
You need to top up the pressure immediatley to approx 1 BAR (when cold) .
Yes, when the heating is on the hot water expands so the pressure would normally go up. You need to get water into the system, then bleed all the radiators (top down) until water bubbles out, and if need be get water into the system after each radiator check as necessary. As gasman has said, do this when the system is cold.
Question Author
Hi

Thanks for the fast response, I was concerned but I'm just waiting for it to cool down and I'll sort it out. Final question, do I bleed the radiators when the systems cold?
You can bleed them anytime, But the pressure will be greater when hot due to the thermal expansion in a sealed system. So to gain an accurate pressure guage reading it is best recorded when cold. Hot it could be anything upto approx 2.5BAR.
Question Author
Again, many thanks Gasman.

1 to 5 of 5rss feed

Do you know the answer?

Topping up CH Combi Boiler

Answer Question >>