Can You Be Fined For Emptying A Swimming...
Civil0 min ago
We have a central heating system that is about four years old. In the kitchen there is a fan heater connected to the heating system. It's gradually been coming on less and less frequently and now doesn't work at all on hot, although it blows cold air. It looks as though it needs bleeding but that made no difference. There is an inlet pipe (braided metal) which feels warm. The outlet pipe is cold. The bleed valve is connected to the end of the inlet pipe. Is it possible that the inlet and outlet pipes were installed the wrong way round? Is it difficult to swap the pipes over? There are stop valves in each connection to the blower.
No best answer has yet been selected by Mendipman. Once a best answer has been selected, it will be shown here.
For more on marking an answer as the "Best Answer", please visit our FAQ.It shouldn't matter which way round the connections are. Check the boiler pressure is ok or that the loft ball valve is free and only bleed when the boiler is off. In order to check the radiator operation close off all other rads so that all the flow goes through this rad, this should clear any air locks or minor blockage.
If this makes it work, open all other rads, if it then stops working the system needs balancing and/or the pump speed needs increasing to get more flow.
If it will not work at all or is just warm, check the valves are open and that the braided pipe is not kinked or internally damaged or there is not an internal blockage in the radiator or supply pipe.
Sorry, we can't find any related questions. Try using the search bar at the top of the page to search for some keywords, or choose a topic and submit your own question.