Hi Pablo7, The venturi test point is located behind the combustion chamber cover at the top left of the boiler It is a small tube that sticks up from the top of the heat exchanger lid left of the flue outlet. Also check the Air pressure control damper is not stuck or need adjusting this is located to the top right hand side just below the fan. Try cleaning the posative and negative spigots of the Air pressure switch while you're at it , located below the combustion chamber to the right of the gas valve. Then finally check that the flowmeter is not faulty and the filter is not clogged up. This should be a T shaped fitting with a wire coming out of it, an arrow pointing right and a nut on the bottom of it. It will be attatched to the incoming cold water pipe inside the boiler at the bottom before it bends up and goes into the combustion chamber. If evething checks out OK then the waiting time is operating and it will require a new Circuit board. Hope this Helps. By the way I should point out that it is illegal for a non CORGI registered engineer to remove the combustion chamber cover....!!!!