Central heating problem

Avatar Image
Kelvin | 22:51 Tue 11th Mar 2008 | Interiors
2 Answers
I just drained my central heating system to install a new radiator. When I refilled it, bled all the air out and turned the heating back on, the boiler only stayed lit for a few minutes than cut out before the radiators were hot. The pipes around the pump in the airing cupboard are scorching but the radiators are cold. Any suggestions?
Gravatar

Answers

1 to 2 of 2rss feed

Best Answer

No best answer has yet been selected by Kelvin. Once a best answer has been selected, it will be shown here.

For more on marking an answer as the "Best Answer", please visit our FAQ.
You've got an airlock somewhere. Possibly around the main pump area - could be it is just spinning air around.
The boiler went off because the water in the heat exchange was hot enough.
Question Author
Cheers Buildersmate,
Turning on rads one at a time and further bleeding, along with turning the pump up a notch sorted the problem.