Polly1958 | 18:08 Fri 13th Jan 2012 | How it Works
2 Answers
My mum has Vokera gas boiler,which I know very little about.A few weeks ago I stayed with her and it was making an awful lot of noise.When I looked at the dial the pressure was into red,I found the manual and decided to turn it off, as I wasn't sure how to get the pressure back up.When my husband came the following day he adjusted the pressure as per instructions and it was fine.The problem is that it's losing pressure now in less than a week,is this normal?
Gravatar

Answers

1 to 2 of 2rss feed

Best Answer

No best answer has yet been selected by Polly1958. Once a best answer has been selected, it will be shown here.

For more on marking an answer as the "Best Answer", please visit our FAQ.
No its not. Something is leaking water. Start by looking at the pressure relief valve (that may be leaking water below it's normal relief escape pressure of 3 to 4 bar).
Question Author
Thanks and apologies for the delay in replying builders mate.I have just heard from mum and she's had it fixed,it sounds like it was as you said.